Experimantal setup for investigation of free-convection heat exchange on finned tubes of air-cooling heat exchanger

Authors: Sidorik G.S.
Published in issue: #2(2)/2016
DOI: 10.18698/2541-8009-2016-2-18


Category: Power, Metallurgic and Chemical Engineering | Chapter: Machines and Devices, Processes of Refrigeration and Cryogenic Engineering, Air Conditioning

Keywords: air cooling apparatus, free convection, convective flow, heat transfer coefficient, reduced degree of blackness, calorimeter tube, Nusselt number, Rayleigh number
Published: 21.10.2016

The purpose of this work was to develop an experimental setup for investigation of free convection on the finned calorimeter tube. Empirically we obtained the dependence of the end heat loss in the calorimeter tube on the temperature bushings. We made a comparison with Mikheyev data for free convection on a smooth calorimeter tube and found that the error of the experimental data was less than 3%. We developed a technique and carried out experimental studies of the calorimeter finned tube with geometric parameters d x d0 x h x s x Δ x l = 56 x 26 x 15 x 2,5 x 0,5 x 330. For convective heat transfer we obtained experimental dependences of Nusselt numbers on Rayleigh numbers for the tubes with varying degrees of blackness, which are consistent with each other and with the known laws.


References

[1] Chumak I.G., Chepurnenko V.P. Kholodil’nye ustanovki [Cooling plants]. Moscow, Agropromizdat Publ., 1991. 495 p. (in Russ.).

[2] Bessonnyy A.N., Kuntysh V.B. Osnovy rascheta i proektirovaniya teploobmennikov vozdushnogo okhlazhdeniya [Calculation and engineering basis of air cooled exchanger]. Sankt-Petersburg, Nedra Publ., 1996. 512 p. (in Russ.).

[3] Kuntysh V.B., Bessonnyy A.N. Primery raschetov nestandartizirovannykh effektivnykh teploobmennikov [Calculation examples for nonstandardized effective heat exchangers]. Sankt-Petersburg, Nedra Publ., 2000. 300 p. (in Russ.).

[4] Korolenko Yu.A. Heat output from lateral pipe bundle to the air in case of natural convection. Izvestiya TPU. Inzhiniring georesursov [Bulletin of the Tomsk Polytechnic University. Geo Assets Engineering], 1962, vol. 110, pp. 26-33. (in Russ.).

[5] Mil’man O.O. Experimental investigation of heat transfer during the natural circulation of air in a model of an air condenser with an exhaust shaft. Teploenergetika, 2005, no. 5, pp. 16-19. (Eng. version of journal: Thermal Engineering, 2005, vol. 52, no. 5, pp. 369-373.)

[6] Samorodov A.V. Sovershenstvovanie metodiki teplovogo rascheta i proektirovaniya apparatov vozdushnogo okhlazhdeniya s shakhmatnymi orebrennymi puchkami. Avtoref. kand. dis. kand. tekhn. nauk [Improving method of thermal calculation and air-cooling engineering of unit with shaft ribed beams. Kand. tech. sci. diss. thesis]. Arhangel’sk, 1999, pp. 3-22 (in Russ.).